Low Pressure Chiller Refrigerant Protection System
![]() |
Low Pressure Chiller Refrigerant Protection System
Automatically neutralizes abnormal pressure build-up in chiller SavAll Model 500 -2000 Specifications Manual SavAll Model 2500-5000 Specifications Manual |
Operational Overview
The Primary Function
of the Redi Controls SavAll Refrigerant Containment System is to
provide fully automatic emergency transfer of liquid refrigerant from the
evaporator of a centrifugal chiller to a safe storage vessel for temporary
containment in the event of an evaporator over-pressure condition. Once the
over-pressure condition subsides, or is restored to normal, the liquid
refrigerant automatically returns to the evaporator.
Because operation of the SavAll System is completely automatic, and does not require operator interaction to function, chiller down time and potential catastrophic loss of refrigerant, due to evaporator over-pressurization, are virtually eliminated.
Operation of the SavAll System is completely passive, relying solely upon pressure differential and gravity to function. The system is totally non-electric, which means there are no electronic controls, sensors, motorized valves or pumps to fail. Because the system is non-electric, it will continue to protect the chiller's refrigerant charge during periods of power outage.
As a Secondary Function, the SavAll System serves as a permanent on-line refrigerant storage vessel for use during chiller servicing and repair.