Purge Guard
![]() |
Redi Controls Purge Guard Purpose of the Purge Guard There are certain control malfunctions which can occur with any thermal type purge regardless of make or model, such as welded relay contacts, locked-up microprocessor, or a unit accidentally left in manual mode, which can cause the pump-out compressor to latch-up in a non-stop running condition. Under these conditions the purge unit's built-in Excessive Purge Fault safety cannot stop the pump-out compressor and can result in catastrophic loss of refrigerant. The purpose of the Purge Guard is to detect the above condition and terminate pump-out activity. Since the Purge Guard functions independently from the purge unit’s microprocessor control it is able to terminate pump-out activity irrespective of the nature of the malfunction. Product Information & INSTALLATION MANUAL Wiring Instructions for Various Model Purgers |
How the
Purge Guard
works
A Purge Unit's non-condensable pump-out cycle time is
normally about 2 or 3 minutes. A cycle time in excess of 2 or 3 minutes is
generally an indication that a problem is developing.
The Purge
Guard monitors
pump-out compressor run time during each pump-out cycle. If
pump-out run time exceeds what is predetermined as a Normal Maximum Time,
as pre-set on the Purge Guard
dip-switch, (e.g. 30 minutes), the
Purge Guard will
automatically lockout purge pump out compressor operation. Purge
activity will remain locked out until manually reset.
It is important to understand the difference between the purge unit’s
normal Excessive Purge Fault and the
Purge Guard
excessive pump-out compressor Run Time.
The Purge Unit's Excessive Purging Fault lock-out occurs whenever the
cumulative pump-out time during any 24 hour period exceeds the maximum allowable
time preset on the purge unit's Fault Time Dip Switch. The
Purge Guard Excessive pump-out compressor
Run Time lockout
occurs whenever the pump-out compressor's ON time exceeds the time
value pre-set on the Purge Guard
Dip Switch.
|